Fire module 4 outputs 48 V

Article Number: A-FU004804FS01
E-number: –

monitoring of alarm devices via inverted voltage (24V) and fuse of 1-4 outputs; Four individually controllable voltage outputs and/or sum control and/or evacuation function (priority input). Constant or pulsating signal on output. Display and button allow system calibration. Indications for which output and what it is alerting for (interruption or short circuit).

By default, the card comes with four F2A fuses that can be secured up to 2 A per output (maximum 8 A total for the entire card). Possible to monitor star networks about 5 loops per output. Monitoring is done with 10k resistance per loop. Possible to set positive (48 V at alarm) or negative (0 V at alarm) logic. Alarm output for securing and/or loop failures. On Display:

  • The number of loops connected.
  • the number of activated cargo exits (via alarm control);
  • Alarm for: loop failure, short circuit and impedance failure.

Where does the card fit? NEO/NOVA FLX M: 2 slots for optional cards. NEO / NOVA FLX L: 2 slots for optional cards. 19 rack module holder: 4 slots for optional cards. DIN rail via the option: DIN module holder.

Recommended environment

Security class (IP-klass)

Recommended mounting

19 rack module holder, FLX L, FLX M

DIN-rail

Yes, possible with the accompanying plastic holder Note! To be mounted horizontally.

Dimensioner (Höjd x Bredd x Djup)

52 x 55 x 120 mm

Net weight

Voltage in (V)

27.3 VDC

Current out

27.3 VDC (24 V)

Number of unsecured (load-) outputs

Type of fuse / ouput

4x F2A (glass)

Alarm via

Changeover relay

Alarm functions

Buzzer alarm in the event of fuse failure and loop interruption.

In-stock article

Yes

Normal dlivery time

Guarantee period

2 years

Producer

Milleteknik AB

Country of origin

Not