Revisions and the edition of this document

The current and most recently published edition of this document is available at www.milleteknik.com.

The validity of this document can not be guaranteed, as new editions are published without prior notice.

Instructions for use in Swedish in original.[1].

Instructions for use, technical data and translations thereof may contain errors. It is always the responsibility of the installer to install the product in a safe manner.

Symbols

Table 1. Symbol Explanation

Symbols

Denomination

Explanation

warning.png

Warning

Risk of electric shock, improper installation or hot surfaces. Appears in some manuals

Note.png

Note

Used for supplementary information that clarifies the text.

caution.png

Caution/Important

Indicates the risk of equipment damage or malfunction. Also used for information that is important but not security-related

tip.png

Tips

Displays practical advice or shortcuts for installation, operation, or service.

ce-marking-logo-kov.jpg

CE marking

The product complies with applicable EU directives and harmonised standards.

ReadTheManual.png

Read the manual

Please read manual before installation and service.

soptunna_atervinning.ai

Do not dispose of in household waste

The product is covered by the WEEE Directive and must not be disposed of with household waste, it must be recycled and delivered to a recycling centre.

Recycle001.svg

Recycling

Packaging, products and other materials that do not contain electronics must be recycled in accordance with local environmental regulations.



Variant overview NOVA

Table 2. Variant overview

Product name

Certified name

Motherboard: PRO1

Motherboard PRO2:

Motherboard PRO2 v3

Motherboard: PRO3

NOVA 12V 10A FLX S

12 V meets the requirements but is not certified.

-

-

-

x

NOVA 12V 10A FLX M

-

-

-

x

NOVA 12V 10A FLX L

-

-

-

x

NOVA 24V 5A FLX S

NOVA 25 50-FLX-S

X

X

-

X

NOVA 24V 10A FLX S

NOVA 25 100-FLX-S

X

X

-

X

NOVA 24V 5A FLX M

NOVA 25 50-FLX-M

X

X

-

X

NOVA 24V 10A FLX M

NOVA 25 100-FLX-M

X

X

-

X

NOVA 24V 15A FLX M

NOVA 25 150-FLX-M

X

X

X

-

NOVA 24V 25A FLX M

NOVA 25 250-FLX-M

X

X

X

-

NOVA 24V 5A FLX L

NOVA 25 50-FLX-L

X

X

-

X

NOVA 24V 10A FLX L

NOVA 25 100-FLX-L

X

X

-

X

NOVA 24V 15A FLX L

NOVA 25 150-FLX-L

X

X

X

-

NOVA 24V 25A FLX L

NOVA 27 250-FLX-L

X

X

X

-



Read this first!

Electronics, regardless of enclosure, are intended for use in a controlled indoor environment. Mains voltage should be disconnected during installation.

It is the installer's responsibility that the system is suitable for its intended use. Only authorized persons should install and maintain the system.

All information subject to change.

About glass tube fuses on certified devices

There are glass tube fuses on the circuit board's load outputs, these have a tripping time of approx. 150 ms. In the event that a glass tube fuse trips on ONE load output, the voltage on ALL load outputs drops to 0 V for 150 ms.

The installer is responsible for ensuring that there is an energy buffer of at least 150 ms in systems that the battery backup supplies power to or accepts a power failure of 150 ms.

Installation — general information

Installation shall be carried out by a competent electrician in accordance with the applicable national electrical installation rules.

The product is of protection class I and must be connected to a grounded 230 V AC circuit.

  • A main switch according to IEC 60947-1 shall be provided in the fixed installation. The switch should be easily accessible and clearly marked with its function.

  • The area of the supply cable shall be at least 1,0 mm² and fitted with a fuse T 2,5 A (slow-blown) or equivalent.

  • AC and low voltage cables must not be pulled together. Keep separate cable chutes or bundles

  • Check that protective earth (PE) is properly connected before turning on voltage.

  • Ensure free air circulation around the enclosure at least 100 mm, unless otherwise specified. Ventilation openings must not be covered.

  • The product is intended for indoor installation in normal environment (pollution number 2 and indoor class 1).

These general requirements apply to all Milleteknik products with 230 V mains connection.

Requirements for main switch, fuse and cable area

In order to comply with applicable electrical safety requirements, the installation shall be equipped with a main switch according to IEC 60947-1.

Table 3. Main switch and fuse

Component

Requirements

Main switch

A main switch according to IEC 60947-1 shall be included in the installation and be easily accessible. Separated phase (F) and neutral (N)

Fuse

The supply circuit shall be protected by a fuse or automatic fuse with rated current according to the product specification (normally T 2,5 A slow-blown or equivalent). Refer to the device's nameplate.

Fuses

Approved type according to IEC 60127.

Cross-sectional area (230 V)

At least 1,0 mm2

Cable length

In the case of longer wiring, voltage drops should be taken into account so that the operating voltage does not fall below 230 V ± 10% at the unit.

Strain relief

All cables must be properly secured and strain relief checked before energizing the unit.



These requirements apply to all Milleteknik products with 230 V mains connection.

The table below shows recommended cable area for low current installations at different voltages, current strengths and cable lengths. Values are based on copper cable and a maximum voltage drop of approximately 3% to ensure operational reliability.

Table 4. Cable area weak current

V

Current strength (A)

Cable length 10 meters

Cable length 30 meters

Cable length 60 meters

Cable length 100 meters

24V

1 A

0,75 mm2

0,75 mm2

1,5 mm2

1,5 mm2

24V

3A

0,75 mm2

0,75 mm2

1,5 mm2

2,5 mm2

24V

5A

0,75 mm2

1,5 mm2

2,5 mm2

4 mm2

24V

10A

1,5 mm2

2,5 mm2

6 mm2

-*

24V

15A

1,5 mm2

4 mm2

-*

-*

24V

25A

2,5 mm2

6 mm2

-*

-*

24V

40A

4,0 mm2

-*

-*

-*

* Cable area would exceed connector terminal dimensions therefore it is not possible to use cable larger than 6 mm! 2



Component overviews

Component overviewNOVA FLX L

FLX_L_PRO3_oeversikt_och_batteri_siffror.png

Batteries should be placed as in the picture.

Table 5. Component overview

Letter

Explanation

A

Bracket, reversible for wall mounting or 19 "rack.

B

Tamper switch. If alarm class 3 (SSF) is to be met, the tamper contact must be on the wall.

C

Cabinet in powder-coated sheet metal.

E

Space for mounting optional cards (not included).

G

Motherboard, (varies with configuration).

H

Cable entries.

I

Battery fuse.

J

Space for batteries.



Enclosures

Console

The supplied brackets can be attached in two ways: When mounting on a wall, the brackets must sit backwards, against the wall. When mounting in a 19" rack, the bracket must sit at the front of the unit.

Table 6. Console

Letter

Explanation

A

Console is pushed in from the bottom up. Slide the top bracket in first.

B

Clip clicks in when bracket is pushed in correctly.



Important

If alarm class 3 (SSF) is to be met, the cabinet and tamper switch must be mounted on the wall. Optional, Cabinet tamper M/L to put a tamper switch on the wall is available.

Mounting

Use the appropriate screw for mounting on a wall or in a 19" rack. Screws for mounting on a wall or in a rack are not included.

Mounting - wall mounting

  • The products shall be mounted on a stable wall or mounting plate with sufficient bearing capacity for the weight of the enclosure, including batteries.

  • The enclosure is mounted vertically.

  • Use four screws with a diameter of 4—5 mm, depending on the substrate.

  • Recommended distance between screw head and wall should be 1.5-2 mm.

  • For mounting on drywall, wall anchors or expanders should be used.

  • When mounting on concrete or brick, dowels or equivalent fastening are used.

  • For good ventilation, at least 100 mm of free space should be provided above and on the sides of the enclosure.

  • The unit should be mounted at a comfortable working height, normally between 1.4 and 1.8 m above the floor.

  • Avoid placement in direct sunlight, near heat sources, or in environments with high humidity or dust.

  • For outdoor use, only enclosures with the specified IP class for outdoor use shall be used.

  • Installation shall be carried out in accordance with the applicable installation rules and by a competent installer.

Batteries - placement and connection

Connecting batteries in FLX M

Figure 1. Connection of batteries in FLX M. Motherboards may differ depending on the configuration, but connection of batteries takes place in the same way.
Connection of batteries in FLX M. Motherboards may differ depending on the configuration, but connection of batteries takes place in the same way.

Note that cards (4) differ from different configurations.



Table 7. Connecting batteries.

No

Explanation

1

Minus coil for battery cable from 4.

2

Fuse.

3

Plus terminal for battery cable from 4.

4

Motherboard, varies with configuration.

5

Battery cables are located on the system board.

6

Connection for connection of battery box.



Connection of batteries in FLX S, FLX M and FLX L

Battery wiring is mounted on the circuit board upon delivery. Pictures below only show how to connect wiring.

  1. Place the batteries in the cabinet with the battery terminals facing outwards.

  2. Connect the battery cable. Red cable on + and black cable on -.

  • If possible, disconnect mains voltage when replacing the battery.

Figure 2. Wiring diagram for batteries in battery backup
Wiring diagram for batteries in battery backup

Connect the terminals correctly so that you do not damage the equipment.



PRO3 motherboard

Motherboard - description

Figure 3. PRO3
PRO3

The motherboard controls the device and distributes power. See technical data for more information.



Table 8. Circuit Board Overview, Explanation

No .

On circuit board

Explanation

1

J24

Control to power supplies. Internal use.

2

J5

1=Oprio 2=external alarm.

3

D9

LED.

4

JU1

For external LED in door.

5

J11

Reset jumper, used when changing batteries.

6

JU6

Connection for relay cards or communication cards or for updating firmware. Only one card or contact at a time can fit.

7

J29

Connection to fan.

8

J101

Connection to tamper contact.

9

J17

Connection to tamper switch from battery box.

10

J35

Not used.

11

J14

Alarm input from external battery fuse, from battery box.

12 and 13

J10 and J100

Alarm from external option card.

14

D18, D19

LEDs show the status of communication (RS-485).

15

S3

Dip switch

16

P2:1-4

Load outputs

17

P3:1-3

Communication connection, RS-485.

18

P1:1-3

Connection to the mains.



Fuses

Table 9. Fuses on PRO3 / NEO3

Fuse

Type

Explanation

F1

T2.5A

Mains fuse

F3

T16A

Load fuse 1 - (for P2:2)

F4

T16A

Battery fuse

F5

T3A-T10A*

Load fuse 1+ (for P2: 1)

F7

T3A-T10A*

Load fuse 2 + (for P2:3)

*The size of the fuse depends on the battery backup (rated) power outlet (A) .



Warning for replacing fuses (current strength, A)

There is a risk of damage if the fuse is changed to a larger one than what the unit is delivered with. The function of the fuse is to protect the connected load and cables against damage and fire. It is not possible to change the fuse to a larger one to increase the power output.

[sv] Anslut elnät

PacomUty_inkoppling_EL.png

[sv] För in elnätskablage genom kabelgenomföringar på ovansidan skåpet.

Table 10. [sv] Koppla in elnät

[sv] Beteckning

[sv] Förklaring

1

[sv] Vred för nätspänning.

2

[sv] Personskydd / jordfelsbrytare.

[sv] PE

[sv] Jord.

N

[sv] Nolla.

F

[sv] Fas.

x

[sv] Används ej.



Connect load

Max current

The maximum current must not be exceeded. Max current is indicated on nameplate on the device.

Load outputs when SSF certified

In order for certificates to be maintained, only one load output must be used.

If there are one or more connection cards (to increase the number of load outputs), load must be connected there and not on the main board.

Table 11. Load connections

On circuit boards

Explanation

P2: 1

Connection for load 1 +.

P2: 2

Hookup for load 1 -.

P2: 3

Connection for load 2 +

P2: 4

Connection for load 2 -



Dip switch 1-8

Dip-Switch has several different modes:

Table 12. Dip switch 1-8

Dip switch

In mains operation or in battery operation

1

Address for external communication.

2

Address for external communication

3

Address for external communication

4

Address for external communication

5

Sets alarm for mains failure delay

6

Sets alarm for mains failure delay

7

Sets alarm limit for low battery voltage in battery operation.

8

Turns off or turns on LED indication, for everything except alarm in case of triggered tamper contact which is always indicated regardless of dip-switch position.

8 in sequence

Perform battery tests.



Address setting for external communication (Dip switch 1-4)

Dip-Switch S1: 1-4 sets addressing.

Table 13. Addressing Dip-Switch 1-4

Dip: 1

Dip: 2

Dip: 3

Dip:4

Adress 1

ON

OFF

OFF

OFF

Adress 2

OFF

ON

OFF

OFF

Adress 3

ON

ON

OFF

OFF

Adress 4

OFF

OFF

ON

OFF

Adress 5

ON

OFF

ON

OFF

Adress 6

OFF

ON

ON

OFF

Adress 7

ON

ON

ON

OFF

Adress 8

OFF

OFF

OFF

ON

Adress 9

ON

OFF

OFF

ON

Adress 10

OFF

ON

OFF

ON

Adress 11

ON

ON

OFF

ON

Adress 12

OFF

OFF

ON

ON

Adress 13

ON

OFF

ON

ON

Adress 14

OFF

ON

ON

ON

Adress 15

ON

ON

ON

ON



Mains failure delay (dip 5-6)

It is possible to change the time for when the alarm for a power outage should be given. Use the matrix to set the alarm.

Table 14. Mains failure delay

Alarms for mains failure are given after:

Dip 5

Dip 6

3 seconds

OFF

OFF

30 minutes

ON

OFF

60 minutes

OFF

ON

240 minutes (4 hours)

ON

ON



Low battery voltage (dip 7)

Dip: 7 has the same function regardless of whether the unit is in mains or battery operation or whether the tamper switch is held down.

Table 15. Low battery voltage

Alarm for low battery voltage is given when

Dip 7

22,8 V*

ON

24 V

OFF

*25% of battery capacity remains.



LED (dip 8)

LED/battery-test always lights up when the door is open.

Dip-switch 8=ON turns off the LED.

Dip-switch 8=OFF turns on the LED.

Battery test (dip 8)

To do a battery test, dip 8 needs to change position and five seconds need to pass before the test is initiated.

  • If dip 8 in original position is on OFF then switch dip 8 to: ON (wait 5 seconds) and then switch back to OFF.

  • If dip 8 in original position is on ON then switch dip 8 to: OFF (wait 5 seconds) and then switch back to ON.

This activates the battery test after 3-8 seconds. The battery test lasts for about 6 seconds and then the LED flashes yellow quickly. Aged battery alarms may be indicated while the battery test is being performed.

Only reset dip 8 when the test is complete.

Reboot to confirm changes in address, battery and alarm settings to parent system

After the dip-switch has been set for various parameters, the device's software needs to be restarted. This is for the new settings to be stored and take effect.

Important

Rebooting according to this procedure does not   interrupt the output voltage.

Restarting the device software is done by jumpering J11 (PRO3)

Important

Reboot must be done every time a change is made to the device.

NEO cannot be connected to communication/UC.

Reset after battery replacement -PRO3

After battery replacement, the device needs to measure the capacity of new batteries and clear previously set battery capacity. All alarms are cleared from the units memory, statistics remains and can not be cleared.

  • Insert jumper on J11 and remove jumper on J11

After doing step, the battery capacity is cleared in the units memory and is ready to read the new battery capacity.

This procedure needs to be done each time the batteries are replaced or when connecting a battery box.

Note on test of batteries

At start-up, it takes 72 hours before the system performs battery tests. This is to ensure fully charged batteries and to collect averages / history for at least 72 hours. Thereafter, every four hours, a qualified cell sample of the batteries is performed.

Note on start-up with short-circuited batteries

Peak current at start-up with short-circuited batteries: Up to 30 A p-p for 200 ms. Always follow the start-up procedure.

Card Description - Relay Card NOVA Series (PRO3)

Relay card - description, connections and alarm outputs.

  • All fault arm relays must be in the drawn state. Check that there is a gap between CO and NC. Put the measuring instrument on continuity measurement and test closure. This should then indicate a short circuit.

  • All relay outputs are normally live and give an alarm in the event of no voltage.

Relaekort_PRO3.png

No .

Terminal no.

The relay is normally energized.

Alarm type / explanation

1.1...1.4

P4:1

-

GND, protective earth

P4:2

-

RX

P4:3

-

TX

P4:4

-

+5V

2

JU5

-

Connection to motherboard.

3

D2-D6

-

Indicator diode, lit green when OK.

4

P5:10-12

NC, COM, NO

Alarm from tamper switch, (optional for NEO and EN54).

5

P5:7-9

NC, COM, NO

Low system voltage.

6

P5:4-6

NC, COM, NO

Alarm for fuse failure, charger failure overvoltage, charger failure undervoltage, battery not connected, low battery voltage in case of mains failure and aged battery*.

*NOVA only.

7

P5:1-3

NC, COM, NO

Mains failure alarm.

Multiple units into one parent system

To connect several units to a higher system, the load-minus between several battery backups must be connected together.

Fler_BB_systemminus.png

Commissioning - how to start the unit

  1. connect load, alarm and possibly. other connections.

  2. Connect batteries

    1. Connect / switch on fuses

  3. Screw the mains cable into the terminal block and attach the terminal block to the motherboard.

    1. Switch on mains voltage.

Connect in this order

To minimize the risk of errors that may occur in connection with a short circuit, connections to the motherboard must be made in this order.

Anslutningsordning_PRO3.png
Table 16. Connect in this order

Nr

Explanation

1

Connect alarm.

2

Connect load.

3

Connect batteries

4

Connect mains.



Important

For setting dip switches and addressing — see online manual via QR code.

The unit works normally when the indicator LED on the outside of the cabinet door lights up with a solid green light. See front panel for other status indications.

It may take up to 72 hours before the batteries are fully charged.

System test

Test the connected device by performing a system test afterwards commissioning.

Important

Let the batteries charge for a couple of hours, use a multimeter to measure the voltage on each battery. The voltage must be at least 12.7 V per battery.

  • Switch on incoming mains voltage.

  • Indicator LED on the outside of the cabinet door lights up with a solid green light. Disconnect the mains voltage to check that the unit is operating in battery mode and alarms.

  • LED on the cabinet door indicates, see panel for alarm type.

  • Switch on incoming mains voltage. Indicator LED, on the outside of the cabinet door, lights up with a solid green light. Normal operation.

Recovery

Reset the unit by completely de-energizing the unit.

Disconnect battery wiring and mains voltage and reconnect after 5 seconds.

Alarm displayed on cabinet door

In normal mode, the indicator LED shows a solid green light.

222-041_2019.ai
Table 17. The indicator diode shows.

The indicator diode (LED) shows

Explanation

Solid green light

Normal operation.

Slow green flashes

Sabotage alarm.

Fast green flashes

Mains failure.

Solid yellow light

Low battery voltage.

Slow yellow flashes

Aged batteries.

Rapid yellow flashes

Disconnected batteries or battery cell shortage.

Solid red light

Overvoltage or undervoltage or charger fault.

Slow red flashes

Low system voltage.

Rapid red flashes

Blown load or battery fuse has blown.

No light / off

Deep discharge protection is activated. (System shutdown).



When operating system: If the indicator LED is off, deep discharge protection has come into force.

Notice

If the indicator light flashes every 15 seconds, the battery is fully charged and the charge is in rest phase to extend battery life. In the event of a power failure during the rest phase, the battery backup switches to battery operation as usual

Adjustment of tamper switch

SABK_PLIERS_INSTRUCTION.eps

The tamper switch lever must be in the closed position when the cabinet door is closed. If the alarm goes off ("tamper alarm"), the lever may needs to be adjusted.

The lever is adjusted by the following steps:

  1. Pinch with pliers in the middle of the lever.

  2. Carefully adjust the lever in the desired direction (up / down).

  3. Check by closing the door. A click is heard when the contact is closed.

Notice

Tamper switch will not give an alarm when closed and locked the door.

Maintenance

The system with the exception of batteries is maintenance-free when installed in an indoor environment.

Check the fan annually. The fan should rotate smoothly without any noise. Clean the fan from dust and dirt. The fan must be replaced if it does not rotate smoothly or is so dirty that it cannot be completely cleaned. If the fan does not work well, the air flow in the unit will be obstructed, which leads to an increase in heat in the enclosure, which can lead to a deterioration of the battery capacity and to a significantly shorter battery replacement interval.

About batteries

Batteries generate electricity through a chemical process and there is thus a natural degradation of capacity. The biggest factor in battery life is temperature. The higher the temperature, the shorter the battery life. The date of manufacture stamped on the battery and the service life (as stated by the battery manufacturer). An ideal temperature is 20 °C both in operation and in storage. Higher ambient temperature greatly reduces the service life. Thus, actual lifespan varies when used. Batteries should be replaced after half specified (from the battery manufacturer) lifetime for safe operation. Batteries purchased through the manufacturer of the battery backup have a lifespan (from the battery manufacturer) of between 10-12 years with recommended replacement after 5-6 years.

Batteridegradering.png
Table 18. [sv] Tillverkares angivna livslängd och rekommenderat batteribyte

[sv] Tillverkarens angivna livslängd[a]

[sv] Batteri i drift bör bytas efter[b].

[sv] 3-5 år

[sv] 2-3 år

[sv] 6-9 år

[sv] 3-5 år

[sv] 10-12 år

[sv] 5-7 år

[sv] 15+ år

[sv] 8-10 år

[a] Gäller vid helt outnyttjat batteri som är lagrat under optimala förhållanden.

[b] Vid drift i idela omgivningstemperatur, 20 °C.



battery change

  • If possible, disconnect mains (voltage) when replacing the battery.

  • Disconnect battery cables. Note how battery cables are mounted before removing them.

  • Remove battery fuse between batteries.

  • Insert and fasten the new batteries.

  • Connect the battery cables in the same way as before.

  • Connect battery fuse between batteries.

  • Switch on mains voltage. The indicator LED may not be green (up to 72 hours), until the batteries are charged.

  • Test the system by briefly disconnecting the mains voltage, (= the load is driven by the batteries), and then switch on the mains voltage again.

Battery recycling

All batteries must be recycled. Return to manufacturer or return to recycling station.

soptunna_atervinning.ai

Safety Information - Service and Troubleshooting

  • If possible, disconnect the mains supply before starting any work, such as servicing, battery replacement, metering or troubleshooting.

  • Remove the battery fuse/plug before working on the DC side.

  • Check that all cables are properly connected and grounded before re-energizing the unit.

  • The product may contain components that become hot during operation. Avoid touching internal parts immediately after the power has been switched off.

  • If fuses disengage repeatedly see Troubleshooting or disconnect the device and contact Milleteknik technical support.

  • In case of suspicion of damage, liquid ingress or burnt odour, the product must not be used until it has been checked by competent personnel.

  • During operation, the housing should be closed and locked (if the device has a lock).

  • Only authorized service personnel may perform repairs on the device.

  • Use only original fuses and batteries of the same type and value as specified in the manual/product sheet.

Milleteknik is not responsible for damage caused by improper handling, modification or unapproved components.

Troubleshooting

If the device does not work as expected, go through the following checks:

Table 19. Troubleshooting

Problem

Possible cause

Action

No output voltage.

No mains voltage, fuse triggered or battery failure.

Check the supply, fuses and battery connections.

Battery does not charge.

Faulty battery connection or battery fuse has blown.

Check battery cables and replace battery fuse if necessary.

The device starts but alarms.

Batteries not sufficiently charged or faulty load or battery.

Wait 72 hours until the batteries are fully charged. Ensure that the connected load does not exceed the rated current.

LED flashes.

Information, warning or error.

See panel or manual for explanation.

Fuses blow frequently.

Short circuit or overload.

Check connected devices, change the fuse only after the cause is fixed.

The device gets hot

High load or insufficient ventilation

Check that the rated current is not exceeded and that air flow is present around the housing.



If the problem persists after these checks, contact Milleteknik support and provide the product name, serial number and a brief error description.

NOVA product sheet

SSF1014 certified battery backup with communication

Figure 4. NOVA FLX L
NOVA FLX L

NOVA FLX L can be mounted on a wall or in a 19" rack.



Technical specifications

These technical specifications are subject to change without notice.

Name, article number and e-number

Table 20. Name, article number and email number.

Name

Article number

E-number

NOVA 24V 10A FLX L

FL01P30024P100-SSF

52 135 70

NOVA 24V 5A FLX L

FL01P30024P050-SSF

52 135 69



About NOVA FLX

NOVA FLX is mainly used in safety systems where SSF 1014 approved battery backup is required or where the requirements are higher. Requirements such as better flexibility, more alarm functions, longer backup operating times or where the battery backup needs to handle higher loads.

The NOVA series is system certified according to SSF1014 together with most systems on the Swedish market. Milleteknik has the right to sell two different systems on the Swedish market; Sentrion NOVA The series has communication via RS485 to Sentrion S4, S4 DUO and CISS. Integra. Together with MOVEO kit (optional) there is RS232 communication with Integra MOVEO and MOVEO XL.

Flexibility

NOVA FLX S can have an extra battery box. NOVA FLX M and NOVA FLX L with 1-4 extra battery boxes *. NOVA FLX M and NOVA FLX L with battery shelves in 19 ”rack *. * The battery boxes and shelves are connected via a 9-pin connector. The battery box has room for up to 2 pcs. 45 Ah batteries per battery box. Battery shelves have room for 2 pcs. 45 Ah batteries (Medium) and up to 2 pcs. 150 Ah batteries (Large) per each battery shelf.

Fixed installation

The product is intended for fixed installation. The battery backup must be installed by a qualified installer.

Area of use

NOVA FLX mostly used for: Access control system, burglar alarms, (integrated security systems), in public environments such as schools, offices and commercial properties.

Installation video

Regulations and certifications

Standards that product (s) meet and are approved for

Table 21. SBF

SBF 110:8



Table 22. SSF

SSF1014 Alarm class 1-4 (burglar alarm).

SSF1014, Issue 5.



Table 23. Certificate and certificate number

Certificate number, SBSC

Designation SBSC

No. 18-246

NOVA 27 250-FLX, NOVA 27 150-FLX, NOVA 27 100-FLX, NOVA 27 50-FLX, NOVA 13 100-FLX, NOVA 27 100-XS2, NOVA 27 50-XS2, NOVA 27 30-XS2, NOVA 13 100-XS2, NOVA 13 50-XS2

No. 20-117

NOVA 27 50-FLX S • NOVA 27 100-FLX S • NOVA 27 50-FLX M • NOVA 27 100-FLX M • NOVA 27 150-FLX M • NOVA 27 250-FLX M • NOVA 27 50-FLX L • NOVA 27 100-FLX L • NOVA 27 150-FLX L • NOVA 27 250-FLX L Unison Facility Cabinet



Table 24. Certificate number RiSE

Certificate number, RiSE

SC0204-19



Requirements that the product meets

Table 25. The product meets the following requirements.

EMC:

EMC Directive 2014 / 30EU

CE:

EC Directive in force: 765/2008

Emissions:

EN61000-6-:2001 EN 55022:1998: -A 1:2000, A 2:2003 Class B, EN61000-3-2:2001, EN 55032 (replaces EN 55022)

Machinery Directive

The product is part of electrical systems, is subject to the relevant electrical and safety directives and is not a machine according to the Machinery Directive (2006/42/EC).

Ecodesign

Milleteknik's products are intended for professional use and are therefore not directly covered by the Ecodesign Regulation (EU 2019/1782). As some components may be covered, we nevertheless disclose relevant information to give our customers confidence in their choice



Efficiency (%)[a]

Standby consumption, typical (W):

89%

3.38 W

89%

3.38 W

[a] At rated load.

ce-marking-logo-kov.jpg
soptunna_atervinning.ai

Reserve operating times, power outlet and load output current

Charging current for batteries and battery capacity

The unit reads the connected system load and charges the batteries with available residual current from the power supply. The device performs qualified* battery tests and notifies  when batteries need to be replaced. The batteries are charged gently to extend their life and protection is available against overcharging.

Table 26. [sv] Laddström

12 V / 24 V

Maximum charging current for batteries

NOVA FLX L

6 A



The battery backup has controlled charging ** (controlled charging) which prevents batteries from being overcharged and extends their service life significantly. The NOVA series must be used with AGM batteries.

Table 27. Battery capacity in 24 V units

24 V

Battery capacity

Maximum battery capacity with 1 battery box

Maximum battery capacity with 2 battery boxes

Maximum battery capacity with 3 battery boxes

Maximum battery capacity with 4 battery boxes

NOVA FLX L, 24 V

45 Ah (2 pcs 45 Ah)

90 Ah (4 x 45 Ah)

135 Ah (6 x 45 Ah)

180 Ah (8 x 45 Ah)

225 Ah (10 x 45 Ah)



Power outlet NOVA FLX

NOVA 24V 5A FLX L

Unit without battery box

Unit with

1 battery box

Unit with

2 battery boxes

Unit with

3 battery boxes

Unit with

4 battery boxes

Battery

2 pcs. 45 Ah

4 st 45 Ah

6 st 45 Ah

8 st 45 Ah

10 st 45 Ah

Max battery capacity

45 Ah

90 Ah

135 Ah

180 Ah

225 Ah

According to. SSF1014, Alarm Class 1-2

3.7 A

7.4 A

11.2 A

14.9 A

18.7 A

According to. SSF1014, Alarm Class 3-4

1.5 A

3.0 A

4.5 A

6.0 A

7.5 A

Imax A (max discharge current)

5 A

5 A

5 A

5 A

5 A

Imax b (max charging current)

5 A

5 A

5 A

5 A

5 A

Imin is always 0 A.

NOVA 24V 10A FLX L

Unit without battery box

Unit with

1 battery box

Unit with

2 battery boxes

Unit with

3 battery boxes

Unit with

4 battery boxes

Battery

2 pcs. 45 Ah

4 st 45 Ah

6 st 45 Ah

8 st 45 Ah

10 st 45 Ah

Max battery capacity

45 Ah

90 Ah

135 Ah

180 Ah

225 Ah

According to. SSF1014, Alarm Class 1-2

3.7 A

7.4 A

11.2 A

14.9 A

18.7 A

According to. SSF1014, Alarm Class 3-4

1.5 A

3.0 A

4.5 A

6.0 A

7.5 A

Imax A (max discharge current)

10 A

10 A

10 A

10 A

10 A

Imax b (max charging current)

10 A

10 A

10 A

10 A

10 A

Imin is always 0 A.

Permitted average load according to SSF1014 Alarm class 1-4:

Table 28. NOVA 24 V FLX L

Permitted average load according to SSF1014 Alarm class 1-4:

NOVA 24V 5A FLX L

NOVA 24V 10A FLX L

NOVA 24V 25A FLX L

MOVA 24V 25A FLX L

FLX M without battery box according to Alarm class 1-2 / 3-4

3.7 A / 1.5 A

3.7 A / 1.5 A

3.6 A / 1.4 A

3.6 A / 1.4 A

Including 1 pc. Battery box FLX M, according to Alarm class 1-2 / 3-4:

-

7.4 A / 3 A

7.3 A / 2.9 A

7.3A / 2.9A

Including 2 pcs. Battery box FLX M, according to Alarm class 1-2 / 3-4:

-

-

11.1 A / 4.4 A

11.1 A / 4.4 A

Including 3 pcs. Battery box FLX M, according to Alarm class 1-2 / 3-4:

-

-

-

14.8A / 5.9A

Including 4 pcs. Battery box FLX M, according to Alarm class 1-2 / 3-4:

-

-

-

18.7A / 7.5A



Reserve operating times for different alarm classes - overview

Alarm class

Spare operating time in the event of a power failure

Maximum number of hours of battery recharging (80%)

EN54-4

-

24 h

SBF110: 8

30 h + 10 min

24 h

EN50131-6 grades 1-2

12 h

72 h

EN50131-6 grade 3

24 h

24 h

SSF1014 Alarm class 1/2

12 h

72 h

SSF1014 Alarm class 3/4

30 h

24 h

The table shows the requirements for backup operating time and recharging of batteries for different alarm classes.

Circuit boards - Technical data

Technical data, motherboard: PRO 3

Info

Explanation

Short name:

PRO 3

Product description

Motherboard in battery backup with advanced functions and communication to parent system.

Own consumption, with relay card

Less than 100 mA. All relays retracted on external alarm card in normal mode.

Switching time from mains voltage to battery operation

When batteries are idle: <5 microseconds. When batteries are in charge cycle: 0 (none). Batteries rest for 20-day cycles, after which a charging cycle picks up and charges the batteries for 72 hours. If there is a power failure when batteries are in the charge cycle, there is no switching time.

Incoming electricity network

230 V AC -240 V AC, 47-63 Hz.

Fuse on mains

See table: Fuses.

Indication

Indicator diode on circuit board / cabinet door

Alarm

Alarm displayed on indicator LED on the front of the cabinet.

  • Cell fault in battery or unconnected battery.

  • Charger fault, undervoltage.

  • Charger fault, overvoltage.

  • Low system voltage, system voltage below 24.0 V in mains operation.

  • Low battery voltage, below 24.0 V DC in case of mains failure.

  • Power failure alarm.

  • Sabotage switch.

  • Fuse fault.

  • Aged battery

Expanding alarm functions are available via communication or with alarm cards.

Table 29. Fuses

Fuses

Type

5 A

T5A

10 A

T10A

Mains fuse for 24 V units up to 15 A

T2.5AH250V. Ceramic.



Table 30. Protection

Info

Explanation

Deep discharge protection (Yes / No)

Yes. 12 V units protection at 10V, +/- 0.5 V. 24 V units protection at 20, +/- 0.5 V.

Surge protection (Yes / No)

Yes

Overtemperature protection (Yes / No)

Yes

Short circuit protected = (Yes / No)

Yes



Technical data, alarm card for PRO 3 / NEO3

Info

Explanation

Card name:

PRO 3

Version:

1.2

Product description

Motherboard in battery backup with advanced functions and communication to superior systems.

Recommended environment

Indoors, class 1. Ambient temperature: + 5 ° C - 40 ° C.

Protection class

IPX0

Recommended installation

NOVA Series (only 5 A and 10 A)

Input voltage

13.6 VDC, 27.3 VDC

Self-consumption

40 mA

Alarm via

Alternating relay

Number of alarm outputs

4 pcs

Certified according to

EN 50131-6, SBF 110: 8, SSF1014, Meets alarm class 4, SSF 1014, edition 5

Certificate number (SBSC)

20-117

The product meets the requirements according to

CE directive according to: 765/2008, EMC Directive 2014 / 30EU, Emission: EN61000-6-: 2001, EN55022: 1998: -A1: 2000, A2: 2003 Class B, EN61000-3-2: 2001, Immunity: EN61000- 6-2: 2005, EN61000-4-2, -3, 4, -5, -6, -11. SS-EN 50 130-4: 2011 Edition 2 & SSF1014 Alarm class 1-4 (Burglar alarm).

Producer

Milleteknik AB

Country of origin

Sweden

Table 31. Alarm overview

Alarm overview in alphabetical order

Relay 1 * / Alarm output 1

Relay 2 * / Alarm output 2

Relay 3 * / Alarm output 3

Relay 4 * / Alarm output 4

Communication (P5: 1-9)

Indicator LED on main card and LED on door.

Network outages

X

-

-

-

X

X

Fuse fault

-

X

-

-

X

X

Sabotage switch

-

-

-

X

X

X

Fan fault

-

-

-

-

X

-

Charger fault, overvoltage

-

X

-

-

X

X

Charger fault, undervoltage

-

X

-

-

X

X

Cell fault or unconnected battery

-

X

-

-

X

X

Low system voltage. **

-

-

X

-

X

X

Low battery voltage (<24.0 V DC) or power failure

-

X

-

-

X

X

Overtemperature

-

-

-

-

X

-

Undertemperature

-

-

-

-

X

-

Undertemperature

-

-

-

-

X

-

Short battery life left

-

-

-

-

X

-

Aged battery

-

X **

-

-

X **

X **

Overcurrent 100%, minute average

-

-

-

-

X

-

Overcurrent 80%, daily average

-

-

-

-

X

-

Overcurrent 175%, second average

-

-

-

-

X

-

* Alarm on potential-free relay contact.

*** Not on NEO battery backups.



Table 32. RS-485 on relay board

RS-485 on P4: 1-4

Explanation

P4:1

GND

P4:2

RX

P4:3

TX

P4:4

+5V



Power supply

Power supply - Technical Data LRS-150-24

In:

NOVA 24V 5A FLX L

Info

Explanation

Output voltage

27.3 V

Output current:

0 A - 6.5 A

Output voltage, ripple

200 mVp-p

Overvoltage

28.8 V - 33.6 V

Voltage recharge, ripple / current limitation

Less than 0.6 Vp-p

Efficiency

89%

Current limitation

110% - 140%

Constant voltage

+/- 0.5%

Regulatory accuracy

+ / - 1.0%

Input current (230 V)

1,7 A

Mains voltage frequency

47 Hz- 63 Hz

Mains voltage

230 V AC - 240 V AC

Brand effect

156 W

Temperature range

-30°C - +70°C

Humidity range

20% - 90% RH non-condensed

Power supply - Technical Data RSP-320-24

In:

NOVA 24V 10A FLX L

Info

Explanation

Output voltage

27.3 V

Output current

0 A - 13.4 A

Output voltage, ripple

150 mVp-p

Overvoltage

27.6 V - 32.4 V

Voltage recharge, ripple / current limitation

Less than 1.2 Vp-p

Efficiency

89%

Current limitation

105% - 135%

Constant voltage

+/- 0.5%

Regulatory accuracy

+/- 1.0%

Input current (230 V)

2 A

Mains voltage frequency

47 Hz- 63 Hz

Mains voltage

230 V AC - 240 V AC

Brand effect

321.6 W

Temperature range

-30°C - +70°C

Humidity range

20% - 90% RH non-condensed

Technical data enclosures

Enclosures - Technical Data FLX L

Info

Explanation

Name

FLX L

Enclosure class

IP 32

Measure

Height: 444 mm, width 438 mm, depth 212 mm

Height units

10 HE

Mounting

Wall or 19 "rack

Ambient temperature

+ 5 ° C - + 40 ° C. For best battery life: + 15 ° C to + 25 ° C.

Environment

Environmental class 1, indoors. 20% ~ 90% relative humidity

Material

Powder coated sheet

Color

Black

Cable entries, number

4

Batteries that fit

2 st 12 V 45 Ah

Place for fan

Yes

Link to the latest information

Products and software are subject to updates, you will always find the latest information on our website.

NOVA

Warranty, support, country of manufacture and country of origin

Warranty 5 years

The product has a five-year warranty, from the date of purchase (unless otherwise agreed). Free support during the warranty period is reached at support@milleteknik.se or telephone, +46 31-34 00 230. Compensation for travel and or working hours in connection with the location of faults, installation of repaired or replaced goods is not included in the warranty. Contact Milleteknik for more information. Milleteknik provides support during the product's lifetime, however, no later than 10 years after the date of purchase. Switching to an equivalent product may occur if Milleteknik deems that repair is not possible. Support may be added (at Millteknik's desrection) after the warranty period has expired.

Manufacturer support

Manufacturers provide support for the life of the product, however, for a maximum of 10 years after the date of purchase. Switching to an equivalent product may occur if the manufacturer deems that repair is not possible. Support costs will be added after the warranty period has expired.

Support

Do you need help with installation or connection?

You will find answers to many questions at: www.milleteknik.se/support

Phone: +46 31-340 02 30

Support is open: Monday-Thursday 08:00-16:00, Fridays 08:00-15:00. Closed 11:30-13:15.

Spare parts

Contacted support for questions about spare parts.

Support after the warranty period

Milleteknik provides support during the life of the product, but no longer than 10 years after the date of purchase. Replacement for an equivalent product may occur if the manufacturer deems that repair is not possible. Costs for support and replacement are added after the warranty period has expired.

Questions about product performance?

Contact sales: 46 31-340 02 30, e-mail: sales@milleteknik.se

Contact us

Milleteknik AB

Ögärdesvägen 8 B

S-433 30 Partille

Sweden

+46 31-34 00 230

www.milleteknik.se

Country of manufacture

Country of manufacture / country of origin is Sweden. For more information, contact your seller.

Designed and produced by: Milleteknik AB

Designed and produced by Milleteknik AB

Product life cycle, environmental impact and recycling

The product is designed and constructed for a long service life, which reduces the environmental impact. The product's service life depends on, among other things, environmental factors, mainly ambient temperature, unforeseen load on components such as lightning strikes, external damage, handling errors, and more. Products are recycled by being handed over to the nearest recycling station or sent back to the manufacturer. Contact your distributor for more information. Costs that arise in connection with recycling are not reimbursed.

soptunna_atervinning.ai

Batteries - recommended, not included

Batteries are not included they are sold separately

Batteries are sold separately.

Battery combinations NOVA FLX L

Battery capacity (Ah)

Battery type

Number of batteries

Batteries in unit

45 Ah

45 Ah

2 pcs.

2 in Battery Backup

90 Ah

45 Ah

4 pcs

2 in Battery Backup

2 in Battery Box 1

155 Ah

45 Ah

6 pcs

2 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

180 Ah

45 Ah

8 pcs

0 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

2 and Batteribox 3

225 Ah

45 Ah

10 pieces.

2 in Battery Backup

2 in Battery Box 1

2 and Batteribox 2

2 and Batteribox 3

2 and Batteribox 4

Certified with battery type

The device is certified with a UPLUS battery that must be used to maintain the certificate.

45 Ah, 12 V AGM battery

Fits in

Number of batteries

NOVA 24V 5A FLX L

2

NOVA 24V 10A FLX L

2

Battery type

V

Ah

Maintenance-free AGM, lead-acid battery.

12 V

45 Ah

Table 33. 10+ Design life * battery

Article number

E-number

Article name

Terminal

Measure. Height width depth

Weight per piece

Make

MT113-12V45-01

5230546

UPLUS 12V 45Ah 10+ Design Life battery

M5 Bult

197x165x170 mm

14.5 kg

UPLUS



Reserve operating times for different alarm classes - overview

The table shows the requirements for backup operating time and recharging of batteries for different alarm classes.

Important

This is a guide and all times are approximate and may differ from actual times. Load, temperature and other factors come into play, which is why exact time can not be provided.

Applies to new batteries.

Amperage and batteries vary with configuration, check if the configuration can handle batteries and amperage.

Table 34. Backup operating times 24 V units - without battery box

Medium current

7.2 Ah

14 Ah

28 Ah

45 Ah

Loading

Backup operating time  (approx.), Minutes

0.5 A

450

820

1650

2350

1 A

260

485

970

1460

2 A

150

280

560

920

4 A

90

165

335

550

6 A

67

125

245

405

8 A

57

105

210

350

10 A

44

80

160

270

12 A

38

70

140

235

14 A

33

60

120

200

16 A

28

50

100

170

18 A

25

45

89

150

20 A

23

42

84

142



Table 35. Backup operating times  24 V units - with battery box, 28 Ah - 70 Ah

Medium current

28 Ah

42 Ah

65 Ah

70 Ah

-

4 batteries

(14 Ah)

6 batteries

(14 Ah)

4 batteries

(20Ah + 45 Ah)

10 batteries

(7 Ah)

Loading

Backup operating time (approx.), Minutes

0.5 A

1650

2090

5574

3440

1 A

970

865

3252

2118

2 A

560

815

1770

1329

4 A

335

490

930

864

6 A

245

360

600

605

8 A

210

310

426

544

10 A

160

240

342

414

12 A

140

210

270

363

14 A

120

180

234

311

16 A

100

150

204

286

18 A

90

130

150

254

20 A

84

126

138

241



Table 36. Backup operating times 24 V units - with battery box, 90 Ah - 155 Ah

Medium current

90 Ah

110 Ah

135 Ah

155 Ah

-

4 batteries

(45 Ah)

6 batteries

(20 Ah + 45 Ah)

6 batteries

(45 Ah)

8 batteries

(20 Ah + 45 Ah)

Loading

Backup operating time (approx.), Minutes

0.5 A

4705

5796

7056

8215

1 A

2928

3582

4392

5070

2 A

1836

2247

2754

3230

4 A

1183

1438

1762

2018

6 A

788

959

1175

1345

8 A

748

861

1048

1150

10 A

570

689

839

920

12 A

499

603

699

765

14 A

427

516

629

655

16 A

404

499

592

590

18 A

359

444

526

520

20 A

340

420

498

495



Table 37. Backup operating times 24 V units - with battery box, 180 Ah - 225 Ah

Medium current

180 Ah

200 Ah

225 Ah

-

8 batteries

(45 Ah)

10 batteries

(20 Ah + 45 Ah)

10 batteries

(45 Ah)

Loading

Backup operating time (approx.), Minutes

0.5 A

9408

12972

11760

1 A

5856

7872

7320

2 A

3672

4548

4590

4 A

2365

2670

2945

6 A

1577

1780

1960

8 A

1500

1558

1800

10 A

1140

1246

1410

12 A

950

1038

1200

14 A

855

890

1055

16 A

810

902

995

18 A

715

802

885

20 A

680

722

840



Subject to typos.

Connection of battery box

Connecting batteries in FLX M

Figure 5. Connection of batteries in FLX M. Motherboards may differ depending on the configuration, but connection of batteries takes place in the same way.
Connection of batteries in FLX M. Motherboards may differ depending on the configuration, but connection of batteries takes place in the same way.

Note that cards (4) differ from different configurations.



Table 38. Connecting batteries in FLX L.

Nr

Explanation

1

+ and - battery cable from battery fuse.

2

Battery fuse.

3

+ and - battery cable from motherboard.

4

Motherboard, varies with configuration.

5

Battery cables from the motherboard.

6

Connection for connecting the battery box.

A

- terminal for battery cable from battery fuse.

B

Battery fuse.

C

- terminal for battery cable for connection to battery backup.

D

Connection for connection to battery backup.



Installation of battery box, what to do in battery backup

Cable gland / knock-out is located on the underside of the battery backup and must be disconnected before mounting.

The unit must be de-energized during installation and connection.

  • Use the wiring that comes with the battery box to meet the wiring from the battery backup. See picture.

klipp_bygel.png

The picture shows cable wiring from the battery backup that meets cables from the battery box

Connection of batteries battery box

Battery wiring is mounted on the circuit board upon delivery. Pictures below only show how to connect wiring.

Warning

Damage to equipment can occur due to incorrect connection.

Figure 6. Wiring diagram for batteries in battery backup
Wiring diagram for batteries in battery backup


Note

The type of fuse between batteries varies with configuration.

Connection to batterybox

FLX_med_batteribox.pdf

The picture also gives an overview of connection points for battery cables and battery fuses.

Table 39. Connecting battery box with battery backup.

Battery cables

Explanation

B1+

Connects to fuse .

B1-

Cable from motherboard is connected to battery .

B2+

Cable from motherboard is connected to battery .

B2-

Connects to fuse .

B3+

Connects to fuse .

B3-

Connected via connector to battery in battery backup .

B4+

Connected via connector to battery in battery backup .

B4-

Connects to fuse .



Table 40. Connection

Number

Explanation

1

Battery fuse.

2

Connect battery backup and battery box with white square connector.



Wiring diagram and jumper

Alarms for tamper contact are connected in series and therefore the loop must be unbroken to the last battery box wiring. Jumper closes the loop on each wiring that goes from battery backup to battery box and in order for an alarm to be given on the tamper connector in the battery box, a yellow jumper on wiring must be cut. Do not cut the jumper on the last wiring in the battery box, as sabotage alarms will not be given in any connected battery backup or battery box.

klipp_bygel.png
BatteryBoxFLX.bmp
Table 41. Wiring diagram and jumper

Number

Explanation

1

IN - incoming connection

2

OUT - outgoing connection

3

Jumper on base on outgoing connection



Table 42. Wiring diagram and jumper

Devices

Yellow jumper - where to cut / not cut

Where the end of the loop should be

Battery backup without battery box

Do not cut the jumper

Jumper should remain in battery backup

Battery backup + 1 battery box

Cut jumper from battery backup

Jumper must remain in battery box 1

Battery backup + 2 battery boxes

Cut jumper in battery backup and from battery box 1

Jumper must remain in battery box 2



Battery backup (NOVA FLX) with 4 battery boxes (NOVA FLX)

Inkopplingsschema_batterier_med_batteribox.psd

Tamper switch when using battery box(-es)

If one or more battery boxes have been connected to the unit, the tamper switch must be connected in series in order for alarms from all units to be given. It is important that the series connection ends at the last tamper contact. The series connection must start in the battery backup unit and return to the last battery box.

All tamper contacts must be in series for everyone to be part of the alarm chain. Therefore, the yellow cable that is in the jackable connector must be cut on all connecting cables, except the last on. The cable must not be cut on the last connection / battery box.

Address and contact details

Milleteknik AB

Ögärdesvägen 8 B

S-433 30 Partille

Sweden

+46 31 340 02 30

info@milleteknik.se

www.milleteknik.com



[1] Translations in languages other than Swedish are indicative only and not safely reviewed. Translation should always be checked against the Swedish original to ensure accurate information